beautypg.com

Rockwell Automation 2706-P42_P43_P44_P72_P74_P92_P94 InView Marquee Message Display User Manual User Manual

Page 101

background image

Publication 2706-UM016D-EN-P - March 2006

InView Protocol 4-35

Response for a Priority Message

Priority Messaging using a Modbus ASCII Transmission

This method writes to the first register in the message queue (40103).
When this happens, the previous message in the queue is replaced
with the new message to be activated. This is an example sending a
Priority Message #0800 to all displays that are on the network.

Transmission:

T

ransmission for Priority Messaging

Response: NONE

Update a Variable using a Modbus ASCII 06 Frame in Broadcast
Mode (Recommended)

This method writes (or loads) variable data to the appropriate variable
registers in all displays. The following is an example of loading
variable 20 (register 40020) with the value of 3656 for all displays on
the network.

Transmission:

Transmission to Update a Variable Register with 06 Frame Broadcast

Response: NONE

Beginning
of Frame

ADDR

FUNC

H.O.

ADDR

L.O.

ADDR

DATA

LRC

Error

EOF

Ready to
rec. resp

:

01

06

00

66

0063

30

CR

LF

Beginning
of Frame

ADDR

FUNC

H.O.

ADDR

L.O.

ADDR

DATA

LRC

Error

EOF

Ready to
rec. resp

:

FF

06

00

66

0320

72

CR

LF

Beginning
of Frame

ADDR

FUNC

H.O.

ADDR

L.O.

ADDR

DATA

LRC

Error

EOF

Ready to
rec. resp

:

FF

06

00

13

0E48

92

CR

LF