Communication Connections 83
Connecting to a DH-485
Network
The network diagrams on the next pages provide examples of how to connect
MicroLogix 1100 controllers to the DH-485 network.
You can connect a MicroLogix 1100 controller to your DH-485 network
directly without using an external optical isolator, such as Advanced Interface
Converter (AIC+), catalog number 1761-NET-AIC, as shown in the
illustrations below, because Channel 0 is isolated within the controller.
We recommend that you use a 1747-UIC USB interface to connect your PC to
a DH-485 network. For more information on the 1747-UIC, see the Universal
Serial Bus to DH-485 Interface Converter Installation Instructions, publication
1747-IN063.
DH-485 Configuration Parameters
When MicroLogix communications are configured for DH-485, the following
parameters can be changed:
See
Software Considerations on page 208
for tips on setting the parameters
listed above.
TIP
Use a 1763-NC01 Series A or later (8-pin mini-DIN to
6-pin DH-485 connector) cable or equivalent to
connect a MicroLogix 1100 controller to a DH-485
network.
DF1 Full-Duplex Configuration Parameters
Parameter
Options
Baud Rate
9600, 19.2 KBps
Node Address
1...31 decimal
Token Hold Factor
1...4
A
TERM
B
COM
SHLD
CHS GND