Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 158

Publication 1763-UM001D-EN-P - March 2011
156 Specifications
MicroLogix 1100 DC Input Power Requirements for 1763-L16BBB Unit
ESD immunity
EN 61000-4-2
4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity
EN 61000-4-3
10V/m, 26…1000 MHz (alternatively, 80…1000 MHz),
80% amplitude modulation, +900 MHz keyed carrier
Fast transient immunity
EN 61000-4-4
2 kV, 5 kHz
communications cable such as EtherNet, RS-232, and RS-485: 1 kV, 5 kHz
Surge transient immunity
EN 61000-4-5
Unshielded communications cable: 2 kV CM (common mode), 1 kV DM (differential mode)
Shielded communications cable: 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply Input: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply Input: 500V CM (common mode), 500V DM (differential mode)
AC/DC Auxiliary Output: 500V CM (common mode), 500V DM (differential mode)
Conducted RF immunity
EN 61000-4-6
10V, 150 kHz…80 MHz
Conducted emissions
EN 55011
AC Power Supply Input: 150 kHz…30 MHz
Radiated emissions
EN 55011
30…1000 MHz
Line related tests
EN 61000-4-11
AC Power Supply Input:
voltage drop: -30% for 10 ms, -60% for 100 ms
voltage interrupt: at voltage greater than -95% for 5 sec.
voltage fluctuation: +10% for 15 minutes, -10% for 15 minutes
DC Power Supply Input:
voltage fluctuation: +20% for 15 minutes, -20% for 15 minutes
General Specifications
Description
1763-
L16AWA
L16BWA
L16BBB
L16DWD
4
8
12
16
20
28
21
14
7
1763-L16BBB and 1763-L16DWD Typical Power Requirements
Calculated Load power (Watts)
In
pu
t
Po
w
er
R
eq
ui
re
d
at
2
4V
D
C
(W
at
ts
)
0