Calculating heat dissipation – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 238
Publication 1763-UM001D-EN-P - March 2011
236 System Loading and Heat Dissipation
Calculating Heat
Dissipation
Use the following table when you need to determine the heat dissipation of
your system for installation in an enclosure. For System Loading, take the value
from the appropriate system loading worksheets on pages 234 or 235.
Heat Dissipation
Catalog Number
Heat Dissipation
Equation or Constant
Calculation
Sub-Total
1763-L16AWA
15.2 W + (0.4 x System Loading)
15.2 W + (0.4 x ______ W)
W
1763-L16BWA
15.7 W + (0.4 x System Loading)
15.7 W + (0.4 x ______ W)
W
1763-L16BBB
17.0 W + (0.3 x System Loading)
17.0 W + (0.3 x ______ W)
W
1763-L16DWD
17.0 W + (0.3 x System Loading)
17.0 W + (0.3 x ______ W)
W
1762-IA8
2.0 W x number of modules
2.0 W x _________
W
1762-IF4
2.0 W x number of modules
2.0 W x _________
W
1762-IF2OF2
2.6 W x number of modules
2.6 W x _________
W
1762-IQ8
3.7 W x number of modules
3.7 W x _________
W
1762-IQ16
5.4 W
(1)
x number of modules
x _________
W
1762-IQ32T
6.8 W x number of modules (at 30.0V DC)
5.4 W x number of modules (at 26.4V DC)
6.8 W x _________ (at 30.0V DC)
5.4 W x _________ (at 26.4V DC)
W
W
1762-IR4
1.5 W x number of modules
1.5 W x _________
W
1762-IT4
1.5 W x number of modules
1.5 W x _________
W
1762-OA8
2.9 W x number of modules
2.9 W x _________
W
1762-OB8
1.6 W x number of modules
1.6 W x _________
W
1762-OB16
2.9 W x number of modules
2.9 W x _________
W
1762-OB32T
3.4 W x number of modules
3.4 W x _________
W
1762-OF4
3.8 W x number of modules
3.8 W x _________
W
1762-OV32T
2.7 W x number of modules
2.7 W x _________
W
1762-OW8
2.9 W x number of modules
2.9 W x _________
W
1762-OW16
6.1 W
x number of modules
x _________
W
1762-OX6I
2.8 W x number of modules
2.8 W x _________
W
1762-IQ8OW6
4.4 W x number of modules
4.4 W x _________
W
Add Sub-Totals to determine Heat Dissipation
W
(1) Only applicable to Series B I/O modules.