Expansion i/o specifications, Digital i/o modules – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 165
Publication 1763-UM001D-EN-P - March 2011
Specifications 163
Expansion I/O
Specifications
Digital I/O Modules
General Specifications
Specification
Value
Dimensions
90 mm (height) x 87 mm (depth) x 40.4 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.59 in. (width)
height including mounting tabs is 4.33 in.
Temperature, storage
-40…85 °C (-40…185 °F)
Temperature, operating
-20…65 °C (-4…149 °F)
(1)
Operating humidity
5…95% non-condensing
Operating altitude
2000 m (6561 ft)
Vibration
Operating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak, 2 hours per axis
Relay Operation: 1.5 g
Shock
Operating: 30 g panel mounted, 3 pulses per axis
Relay Operation: 7 g
Non-Operating: 50 g panel mounted, 3 pulses per axis
(40G DIN Rail mounted)
Agency certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts
Hazardous environment class
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213,
ANSI/ISA-12.12.01)
For all other modules:
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
for all modules
Radiated and conducted emissions
EN50081-2 Class A
Electrical/EMC:
The module has passed testing at the following levels:
ESD immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
For all other modules:
IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity
For 1762-IQ32T, 1762-OB32T, and 1762-OV32T modules
IEC61000-4-3: 10V/m, 80…2700 MHz, 80% amplitude modulation
For all other modules:
IEC1000-4-3: 10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
for all modules