Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 175
Publication 1763-UM001D-EN-P - March 2011
Specifications 173
Input Specifications
Specification
1762-IF2OF2
1762-IF4
1762-IR4
1762-IT4
Number of inputs
2 differential (unipolar)
4 differential (bipolar)
4
4 input channels plus 1
CJC sensor
Update time (typical)
2.5 ms
130, 250, 290, 450,
530 ms (selectable)
Input filter and
configuration dependent
NA
A/D converter type
Successive
approximation
Successive
approximation
Delta-Sigma
Delta-Sigma
Common mode voltage
range
(1)
±27V ±27V NA
±10V
Common mode
rejection
(2)
> 55 dB at 50 and 60 Hz
> 55 dB at 50 and 60 Hz
>110 dB at 50 Hz (with 10
or 50 Hz filter)
>110 dB at 60 Hz (with 10
or 60 Hz filter)
>110 dB at 50 Hz (with 10
or 50 Hz filter)
>110 dB at 60 Hz (with 10
or 60 Hz filter)
Non-linearity (in percent
full scale)
±0.12%
(4)
±0.12%
±0.05% NA
Typical overall accuracy
(3)
±0.55% full scale at
-20…65 °C
±0.3% full scale at 25 °C
±0.32% full scale at
-20…65 °C
±0.24% full scale at
25 °C
±0.5 °C (°F) for Pt 385
NA
Input impedance
Voltage Terminal:
200 K
Ω
Current Terminal: 250
Ω
Voltage Terminal:
200 K
Ω
Current Terminal: 275
Ω
>10
ΜΩ
>10
ΜΩ
Current input protection
±32 mA
±32 mA
NA
NA
Voltage input protection
±30V
±30V
NA
NA
Channel diagnostics
Over or under range or
open circuit condition by
bit reporting for analog
inputs.
Over or under range or
open circuit condition by
bit reporting for analog
inputs.
Over or under range or
open circuit condition by
bit reporting for analog
inputs.
Over or under range or
open circuit condition by
bit reporting for analog
inputs.
(1) For proper operation, both the plus and minus input terminals must be within ±27V (±10V for 1762-IT4) of analog common.
(2) Vcm = 1 Vpk-pk AC
(3) Vcm = 0 (includes offset, gain, non-linearity and repeatability error terms)
(4) Only applicable to Series B I/O modeles.