Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual
Page 170
![background image](/manuals/579860/170/background.png)
Publication 1763-UM001D-EN-P - March 2011
168 Specifications
Signal delay, max. –
resistive load
On Delay: 10 ms
Off Delay: 10 ms
On Delay: 10 ms
Off Delay: 10 ms
On Delay: 10 ms
(max) 6 ms (typical)
Off Delay: 20 ms
(max)
12 ms (typical)
On-delay: 10 ms
(max)
Off-delay: 10 ms
(max)
Off-state leakage, max. 0 mA
0 mA
0 mA
0 mA
On-state current, min.
10 mA
10 mA
100 mA
10 mA
On-state voltage drop,
max.
Not Applicable
Continuous current per
point, max.
2.5 A (Also see “Relay Contact Ratings” on
page 169.)
7 A (Also see “Relay
Contact Ratings” on
page 169.)
2.5 A (Also see
“Relay Contact
Ratings” on page
169.)
Continuous current per
common, max.
8 A
8 A
7 A (Also see “Relay
Contact Ratings” on
page 161.)
8 A
Continuous current per
module, max.
16 A
16 A
30A (Also see
Module Load
Ratings 1762-OX6I
on page 170
8A
Surge current, max.
See “Relay Contact Ratings” on page 169.
See “Relay Contact
Ratings” on page
169.
See “Relay Contact
Ratings” on page
169.
Power supply distance
rating
6 (The module may not be more than 6 modules away from the power supply.)
Isolated groups
Group 1: Outputs 0
to 3
Group 2: Outputs 4
to 7
Group 1: Outputs 0
to 7
Group 2: Outputs 8
to 15
All 6 Outputs
Individually
Isolated.
Group 3:
Outputs 0 to 5
Output group to
backplane isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output
group isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. code
1
Product type code
7
Product code
120
121
124
98
(1) Only applicable to Series B I/O modules
Output Specifications
Specification
1762-OW8
1762-OW16
1762-OX6I
1762-IQ8OW6