PROCESSOR ERRORS
Error
Code
Module Display
Fault Description
xx5B
SLOT xx BAD CFG
G file configuration error – User program G file
size exceeds the capacity of the module.
xx5C
SLOT xx BAD CFG
M0-M1 file configuration error – User program
M0-M1 file size exceeds the capacity of the
module.
xx5D
SLOT xx SI/O ERR
Interrupt service requested is not supported by
the processor.
xx5E
SLOT xx SI/O ERR
Processor I/O driver (software) error.
xx60 thru
xx6F
SLOT xx SI/O ERR
Identifies an I/O card specific recoverable
major error. Refer to the user information
supplied with the card for further details.
xx70 thru
xx7F
SLOT xx SI/O ERR
Identifies an I/O card specific non-recoverable
major error. Refer to the user information
supplied with the card for further details.
xx80 thru
xx8F
SLOT xx SI/O ERR
Identifies an I/O card specific non-recoverable
major error. Refer to the user information
supplied with the card for further details.
xx90
SLOT xx MOD ERROR
Interrupt problem at the specified disabled slot.
xx91
SLOT xx MOD ERROR
The specified disabled slot has faulted.
xx92
SLOT xx INT ERROR
Invalid or non-existent module interrupt.
xx93
SLOT xx MOD ERROR
Unsupported I/O module specific major error.
xx94
MOD IN SLOT xx
In the processor run or test mode, a module
has been detected as being inserted under
power. Code xx94 also can mean that an I/O
module reset itself.