beautypg.com

Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 16

background image

2-2

Installation and Power Up

Publication 1747-6.1

• Before drilling in the enclosure door, all power to the enclosure

must be disconnected. Make sure the drill bit does not contact
equipment and cause damage.

• Do not remove top label until after installation.

• A strain relief tab on the back of the module helps reduce stress

on the interconnect cable when the door is opened. Once the
module is installed, insert the cable under the tab and bend the
tab downward to secure the cable.

• The module has a .8 Nm (7.0 in-lb) mounting torque.

• Insure that the module is grounded. If the DTAM is mounted to a

non-conductive surface, attach a #8 AWG wire from the DTAM
grounding screw to the SLC chassis.

Prepare a cutout for your enclosure door using the measurements
shown below. See the template in Appendix D.

!

ATTENTION: The module has ventilation holes on
the top and bottom of the back cover. If you make
additional holes in the enclosure, cover the module
ventilation holes to protect against metal shavings
entering the module housing.

104.8 mm

(4.125 in.)

95.76 mm

(3.77 in.)

Scrape paint
to ensure
good
ground.

114

.3

m

m

(4

.5

in

.)

1

28.

5

m

m

(5

.0

6

in

.)

Scrape paint
to ensure
good
ground.

3.86 mm dia.
(0.152 in.)
4 holes