Troubleshooting processor faults using the lcd, Troubleshooting processor faults using the lcd -11 – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 91

Troubleshooting
9-11
Publication 1747-6.1
Troubleshooting
Processor Faults
Using the LCD
If you are attached to a processor when a fault occurs, the module
displays a fault code, in hexadecimal format, and a description of the
fault. You may also attach to a faulted processor to view the source of
a fault. The tables below describe the possible fault conditions in SLC
500 family processors.
The characters xx in the following codes represent the slot number, in
hex. The characters xx become 1F if the exact slot can not be
determined.
Slot Numbers in Hexadecimal
Slot
XX
Slot
XX
Slot
XX
0
00
11
0B
22
16
1
01
12
0C
23
17
2
02
13
0D
24
18
3
03
14
0E
25
19
4
04
15
0F
26
1A
5
05
16
10
27
1B
6
06
17
11
28
1C
7
07
18
12
29
1D
8
08
19
13
30
1E
9
09
20
14
10
0A
21
15
PROCESSOR ERRORS
Error
Code
Module Display
Fault Description
0000
NO FAULT
You have attempted to view a fault in a non-
faulted processor.
0001
CORRUPT NVRAM
NVRAM error.
0002
HARDWARE TIMEOUT
Unexpected hardware watchdog timeout.
0003
AUTOLOAD FAILED
Memory module memory error. This error can
also occur when going to the REM Run mode.
0007
1
1. Error codes for 5/03 processor only
TRANSFER FAILED
Failure during memory module transfer of
autoload.
0008
1
CPU SOFTWARE ERR
Internal software error.
0009
1
CPU HARDWARE ERR
Internal hardware error.
0010
WRONG PROC. REV.
The processor does not meet the proper revision
level.
0011
FILE 2 MISSING
The executable program file number 2 is absent.
0012
PROG MEM. ERROR
The ladder program has a memory error.
0013
MEM MOD MISSING
The required memory module is absent or either
S:1/10 or S:1/11 is not set as required by the
program.
0014
INT. FILE ERROR
Internal file error.
0015
CFG. FILE ERROR
Configuration file error.