Troubleshooting module problems using the lcd, Troubleshooting module problems using the lcd -3 – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 83

Troubleshooting
9-3
Publication 1747-6.1
Troubleshooting
Module Problems
Using the LCD
TROUBLESHOOTING CONSIDERATIONS
MODULE DISPLAY
COMM LED
PROBABLE CAUSES
RECOMMENDED ACTION
ERROR 100
LED illuminated red
ROM memory failed checksum
test
Reset module.
ERROR 200
LED illuminated red
RAM failed Read/Write test
Reset module.
ERROR 300
LED illuminated red
Keypad malfunction
Reset module.
ERROR 400
LED illuminated red
Configuration memory failed
checksum test
1. Cycle module power.
2. Reconfigure module. Refer
to chapter 3,
Module Setup
Procedure
.
Backlighting off
LED illuminated red
Insufficient power supply
voltage
Check power supply.
Backlighting flashes on and off
LED illuminated red
Insufficient or unregulated
power supply voltage
Check power supply.
LCD background is solid black
Any
Enclosure is too hot
1. Adjust display contrast,
turn pot clockwise.
2. Operate within temperature
specifications.
LCD characters are out of line
Any
Enclosure is too hot or module
is exposed to sudden
temperature change.
Allow temperature to stabilize.
LCD is difficult to read
Any
Backlighting was Turned Off
Reconfigure module. Refer to
chapter 3,
Module Setup
Procedure
.
LCD characters unintelligible
Any
Water contamination in
module
Correct condition.
Improper initialization
Reset module.
Module Cconfigured for a
foreign language
Reconfigure module. Refer to
chapter 3,
Module Setup
Procedure
.
LCD appears faded or no
display at all
Any
Enclosure too cold
Adjust display contrast, turn
pot counter clockwise.
Module subjected to excessive
heat or humidity
Disconnect module. Contact
your local Allen-Bradley
representative.