Installation and Power Up

2-5

Publication 1747-6.1

You can connect the DTAM module to an SLC 5/04 or later processor
using either of the following methods.

Connection to a DH485 Network Using an Interface Module

Connection to a DH485 Network Using Link Couplers

DTAM

CH

Interconnect Cable
1.8 m (6 ft.) 1747-C10

SLC 5/04 Processor
(1747-L542)

Interface Module
(1747-KE)

9-pin to 9-pin
Connector
(1747-CP3)

DTAM

CH

Interconnect Cable
1.8 m (6 ft.) 1747-C10

Advanced Interface Coupler

1761-NET-AIC

Link Coupler

1747-AIC

Communications

Cable

Belden 9842

Earth Ground

To 24V dc
Power Supply

1747-CP3

To SLC 5/04 Processor

To 24V dc
Power Supply

!

ATTENTION: The DTAM module end of the
interconnect cable has pins that carry 24V dc.
Disconnect the cable at the processor or link coupler to
guard against connector short circuits and possible
damage to the processor.