Troubleshooting msg instruction error codes, Troubleshooting msg instruction error codes -8 – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 88

9-8
Troubleshooting
Publication 1747-6.1
Troubleshooting MSG
Instruction Error
Codes
When an error condition occurs with a Message Instruction (MSG),
the error code and its description are indicated in the Data Monitor
display.
INSTRUCTION ERRORS
Error
Code
Fault Description
02H
Target node is busy. The MSG instruction will automatically reload. If other
messages are waiting, the message is placed at the bottom of the stack.
03H
Target node cannot respond because message is too large.
04H
Target node cannot respond because it does not understand the command
parameters OR the control block may have been inadvertently modified.
05H
Local processor is offline (possible duplicate node situation).
06H
Target node cannot respond because requested function is not available.
07H
Target node does not respond.
08H
Target node cannot respond.
09H
Local modem connection has been lost.
10H
Target node cannot respond because of incorrect command parameters or
unsupported command.
11H
Local file has constant file protection.
12H
Local channel configuration protocol error exists.
13H
Local MSG configuration error in the Remote MSG parameters.
14H
Local communication driver is incompatible with the MSG instruction.
15H
Local channel configuration parameter error exists.
16H
Target or Local Bridge address is higher than the maximum node address.
17H
Local service is not supported.
18H
Broadcast (Node Address 155) is not supported.
19H
Improperly formatted Logical ASCII Address string. String not properly
terminated with a NULL character or the string length does not match the
value in the length parameter.
20H
PCCC Description: Host has a problem and will not communicate.
30H
PCCC Description: Remote station host is not there, disconnected, or shut
down.
37H
Message timed out in local processor.
38H
Message disabled pending link response.
40H
PCCC Description: Host could not complete function due to hardware fault.
50H
Target node is out of memory.
60H
Target node cannot respond because file is protected.
70H
PCCC Description: Processor is in Program mode.
80H
PCCC Description: Compatibility mode file missing or communication zone
problem.
90H
PCCC Description: Remote station cannot buffer command.
B0H
PCCC Description: Remote station problem due to download.
C0H
PCCC Description: Cannot execute command due to active IPBs.
D0H
No IP address configured for the network, -or-
Bad command – unsolicited message error, -or-
Bad address – unsolicited message error, -or-
No privilege – unsolicited message error.