Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 93

Troubleshooting
9-13
Publication 1747-6.1
PROCESSOR ERRORS
Error
Code
Module Display
Fault Description
0032
BAD SQC/SQO INST
A sequencer instruction length/position
parameter points past the end of a data file.
0033
BAD BSL/BSR INST
The length parameter of an LFU, LFL, FFU,
FFL, BSL or BSR points past the end of data
file.
0034
BAD TIMER DATA
A negative value for a timer accumulator or
preset value was detected.
0035
BAD INST IN INTR
TND, SVC or REF instruction is called within
an interrupting or user fault routine.
0036
BAD PID PARAM
An invalid value is being used for a PID
instruction parameter.
0038
RET IN FILE 2
A RET instruction was detected in a non-
subroutine file.
xx39
1
1. Error codes for 5/03 processor only
BAD STxx:LEN
Invalid string length in string file.
xx50
SLOT xx DATA ERR
A rack data error is detected at the slot
specified.
xx51
SLOT xx MOD ERROR
An I/O module runtime error at the slot
specified.
xx52
SLOT xx MOD RMV
A module required for the user program is
detected as missing or removed at the slot
specified.
xx53
MOD IN SLOT xx
At going-to-run, a user program declares a slot
as unused, and that slot is detected as having
an I/O module inserted.
xx54
SLOT xx MISMATCH
A module required for the user program is
detected as being the wrong type.
xx55
SLOT xx MOD ERR
A module required for the user program is
detected as having the wrong I/O count or
wrong I/O driver.
0056
SLOT 00 BAD CFG
The rack configuration specified in the user
program is incorrect.
xx57
SLOT xx COMM ERR
An intelligent I/O module has not responded to
a Lock Shared Memory command within the
required limit.
xx58
SLOT xx SI/O ERR
A specialty I/O module generated a generic
fault.
xx59
SLOTxx SI/O ERR
An intelligent I/O module has not responded to
a command as being completed within the
required time limit.
xx5A
SLOT xx SI/O ERR
Hardware interrupt problem at the specified
slot.