Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 92

9-12
Troubleshooting
Publication 1747-6.1
PROCESSOR ERRORS
Error
Code
Module Display
Fault Description
0016
START AFTER P.F.
Startup protection after power loss. Error
condition exists at powerup when bit S:1/9 is
set and powerdown occurred while running.
0017
1
1. Error codes for 5/03 processor only
PRC/MMOD MISMATCH
NVRAM/memory module mismatch.
001F
1
BAD ONLINE EDIT
A program integrity problem occurred during
an online editing session.
0020
MINOR ERR AT END
A minor error bit is set at the end of the scan.
0021
REM. POWER FAIL
A remote power failure of an expansion I/O
rack has occurred.
0022
WATCHDOG TIMEOUT
The user watchdog scan time has been
exceeded.
0023
INVALID STI FILE
Invalid or non-existent STI interrupt file.
0024
INVALID STI TIME
Invalid STI interrupt interval (greater than 2550
ms or negative).
0025
TOO MANY JSRs
Excessive stack depth/JSR calls for the STI
routine.
0026
TOO MANY JSRs
Excessive stack depth/JSR calls for an I/O
interrupt routine.
0027
TOO MANY JSRs
Excessive stack depth/JSR calls for the user
fault routine.
0028
INVALID FLT FILE
Invalid or non–existent “startup protection” fault
routine file value.
0029
INDEX TOO LARGE
Indexed address reference is outside of entire
data file space (range of B3:0 through the last
file).
002A
INDEX TOO LARGE
Indexed address reference is beyond specific
referenced data file.
002B
1
BAD INDRCT FILE
Invalid indirect address file number.
002C
1
BAD INDRCT ELEM
Invalid indirect address element.
002D
1
BAD INDRCT SUBEL
Invalid indirect address subelement.
002E
1
INVALID DII SLOT
Invalid DII input slot.
002F
1
INVALID DII FILE
Invalid or non-existent DII interrupt file.
0030
SUB NEST TOO DEEP
An attempt was made to jump to one too many
nested subroutine files. This code can also
mean that a program has potential recursive
routines.
0031
UNSUPPORTED INST
An unsupported instruction reference was
detected. Contact Allen-Bradley.