Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 135
8–8
Message Packet Status Codes (STS, EXT STS)
Publication 1770Ć6.5.16 - October 1996
Command
Explanation
STS Code
EXT STS Code
PLCĆ3 word write
-
10
•
There are not at least two bytes of data after the
end of the block address.
•
There is an odd number of data bytes after the end
of the block address.
•
The sum of packet offset and size values specifies
more than 65,535 words.
•
The sum of packet offset and size is greater than
total transaction size.
-
30
The local PLCĆ3 interface module has executed a
shutdown request.
-
40
A backplane error (either memory parity, timeout, or
disconnect) has occurred.
-
60
The processor keyswitch setting does not allow
access.
-
70
The local PLCĆ3 processor is in Program mode.
1
F0
There is an error in converting the block address
(major section > 63, context >15, or section >15).
2
F0
Three or fewer addressing levels specified for a
PLCĆ3 word address.
3
F0
The conversion of a file address to a block address
resulted in more than nine addressing levels.
4
F0
The symbolic address was not found.
5
F0
The symbolic address is of length zero or is longer
than eight bytes.
6
F0
•
The DST file was not found.
•
The DST address does not point to a word (for
wordĆrange writes) or a file (for file writes).
•
The DST address specifies more levels than
required.
•
The first word of the DST location does not exist.
7
F0
•
Any word in the total transaction does not exist in
the DST file.
•
For a file write, the SRC and DST files are not the
same size.
8
F0
The DST file size changed between packets of a
multiĆpacket transaction and became too small for
the total transaction.
9
F0
There are more than 65,535 words in the SRC file.
A
F0
The sum of total transaction size and the word level
PLCĆ3 addressing is greater than 65,535.
B
F0
The source node does not have access to the DST
file.