Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual
Page 34
Chapter 1
Selecting Your Hardware Components
1–15
Allen–Bradley surge suppressors recommended for use with Allen–Bradley
relays, contactors, and starters are shown in the table below.
Device
Coil Voltage
Suppressor Catalog
Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
120 VAC
240 VAC
599-K04
➀
599-KA04
➀
Bulletin 100 Contactor
Bulletin 100 Contactor
120 VAC
240 VAC
199-FSMA1
➁
199-F5MA2
➁
Bulletin 709 Motor Starter
120 VAC
1401-N10
➁
Bulletin 700 Type R, RM Relays
AC coil
None Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12 VDC
12 VDC
700-N22
700-N28
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
24 VDC
24 VDC
700-N10
700-N13
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
48 VDC
48 VDC
700-N16
700-N17
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
115-125 VDC
115-125 VDC
700-N11
700-N14
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
230-250 VDC
230-250 VDC
700-N12
700-N15
Bulletin 700
Type N, P, or PK Relay
Miscellaneous
electromagnetic devices limited to 35
sealed VA
150V max, AC or DC
700-N24
➁
➀
This is an MOV without a capacitor. The 599-K04 or 599-KA04 MOV must be series C or later when used
with triac outputs. Do not use series A or B with triac outputs.
➁
Not recommended for use with triac outputs.