Fixed controller specifications – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual
Page 22
Chapter 1
Selecting Your Hardware Components
1–3
This section provides the specifications for the SLC 500 Fixed Controller.
Description
Specification
Memory Type
Capacitor-backed RAM memory. Battery back-up optional.
Memory Backup Options
EEPROM or UVPROM
Program Memory
1K Instruction Capacity
Capacitor Memory Back-up Time
Battery Life
5 years
Typical Scan Time
➀
8 milliseconds/1K
Bit Execution (XIC)
4 microseconds
Program Scan Hold-up Time after
Loss of Power
20 milliseconds to 700 milliseconds (dependent on loading)
Power Supply Operating Voltage
AC units: 85-265 VAC
47-63 Hz
DC units: 21.6-26.4 VDC (24 VDC
±
10%)
Power Supply Fuse Protection
AC units: 120/240 VAC
1.25A
DC units: 24 VDC
1.6A
Power Supply Inrush Rating
30 Amperes maximum
Maximum Power Requirement
50 VA
➁
24 VDC User Power Output Current
➂
200mA
24 VDC User Power Output Voltage
➂
20.4 - 27.6 VDC (24 VDC
±
15 %)
Wire Size
#14 AWG Max.
I/O Electrical-Optical Isolation
1500 VAC at 1 minute
1747-AIC Link Coupler
Electrical-Optical Isolation
1500 VDC
LED Indicators
POWER, PC RUN, CPU FAULT, FORCED I/O, and
BATTERY LOW
Noise Immunity
NEMA Standard ICS 2-230
Ambient Temperature Rating
Operating: 0
°
C to +60
°
C (+32
°
F to +140
°
F)
Storage: 40
°
C to +85
°
C (-40
°
F to +185
°
F)
Humidity
5 to 95% without condensation
Displacement: .015 inch, peak-to-peak @ 5-57 Hz
Vibration
Acceleration: 2.5 Gs @ 57-2000 Hz
Duration: 1 hr per axis (x, y, z)
Certification
UL listed/
CSA approved
➀
The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication
servicing. Actual scan times depend on your program size, instructions used, and the DH-485
communication.
➁
This specification does not include input and output values. (See page
1-6
.)
➂
This applies only to fixed controllers that have AC line power and DC input circuits.
Fixed Controller
Specifications