Output Specifications
The following table details the output specifications for SLC 500 Fixed I/O
Units.
Outputs
Specifications
Output Voltage
85-265 VAC
Continuous Current (per output)
0.5 Amp at +30
°
C
0.25 Amp at +60
°
C (maximum)
Minimum Load Current
10mA
Triac
Turn-On Time
0.1 milliseconds (maximum)
Triac
Turn-Off Time
10 milliseconds (maximum)
Maximum Off-State Leakage Current
2mA
Maximum On-State Voltage Drop
1.5V @ 0.5 Amps
Maximum Surge Current
10 Amps for 25 milliseconds
➀
Output Voltage
10-50 VDC
Continuous Current (per output)
0.5 Amp at +30
°
C
0.25 Amp at +60
°
C (maximum)
Minimum Load Current
1mA
Transistor Sink &
Source
Turn-On Time
0.1 millisecond (maximum)
Source
Turn-Off Time
1 millisecond (maximum)
Maximum Off-State Leakage Current
1mA
Maximum On-State Voltage Drop
1.5V @ 0.5 Amps
Maximum Surge Current
3.0 Amps for 25 milliseconds
➀
Output Voltage Range
5-265 VAC, 5-125 VDC
Continuous Current (per output)
2.5 Amps (maximum)
Continuous Current (per group)
➁
8 Amps (maximum)
Relay
➂
Maximum Load (per chassis)
1440 VA
Relay
➂
Turn-On Time
10 milliseconds (maximum)
Turn-Off Time
10 milliseconds (maximum)
Maximum Off-State Leakage Current
0mA
Minimum Load Current at 5 VDC
10mA
➀
Repeatability is once every 1 second at +30
°
C. Repeatability is once every 2 seconds at +60
°
C.
➁
Refer to the wiring diagrams for output groupings on the fixed I/O chassis.
➂
Surge suppression across the output device is recommended to protect relay contacts.