Wiring diagram, E-43 – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual
Page 186
for Your Fixed Controller
Appendix E
Wiring and Circuit Diagrams and Voltage Ranges
E–43
Wiring Diagram
PWR OUT
+24VDC
OUT 2 OUT 3 OUT 4 OUT 5 NOT
USED
NOT
USED
DC
COM 1
VDC 2 OUT 6
VDC 1
1
1
OUT 1
OUT 7 OUT 8 OUT 9 OUT 10 OUT 11 NOT
USED
NOT
USED
DC
COM 2
CR
CR
10-50 VDC
CR
CR
CR
CR
OUT 0
+ DC
- DC
+ DC
- DC
10-50 VDC
VAC
NEUT
VDC
VDC
IN 1
IN 3
IN 5
IN 7
IN 9
IN 11
IN 13
IN 15
IN 17
NOT
USED
NOT
USED
NOT
USED
CHASSIS
GND
VDC
VDC
IN 0
HSC
IN 2
IN 4
IN 6
IN 8
IN 10
IN 12
IN 14
IN 16
NOT
USED
NOT
USED
NOT
USED
120/240
VAC
2
2
(Lo)
L2
(Hi)
L1
VDC
Connected
Internally
PWR OUT
COM
10-30
VDC
+ DC
- DC
Sinking Device
85-265
VAC
➀
The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as
the specific application requires.
➁
24 VDC, 200mA user power is available for sensors.
Catalog Number 1747-L30L
(18) 24 VDC Sourcing Inputs,
High-Speed Counter Input &
(12) Transistor Sinking
Outputs