Example heat dissipation calculation, Example worksheet for calculating heat dissipation, This worksheet shows you how to calculate the – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual
Page 141
Control System
Appendix D
Calculating Heat Dissipation for the SLC 500
D–4
If your controller consisted of the following hardware components, you
would calculate heat dissipation as shown in the example worksheet below.
Hardware
Components
Catalog Number
Minimum Watts
Maximum Watts
Fixed Controller
1747-L20A
10.5
15.0
Input Module
1746-IA16
0.425
4.8
Output Module
1746-OA16
1.85
9.3
Peripheral Device
1747-DTAM
2.5
2.5
Example Worksheet for Calculating Heat Dissipation
Procedure
Heat Dissipation
1.
Calculate the heat dissipation for your fixed controller.
Write in the watts (calculated watts or maximum watts, see page D-1)
dissipated by the controller, I/O and specialty modules, and peripheral
device attached to the controller. Add these values together.
Catalog Number Heat Dissipation
Fixed Controller
_________
_________
Expansion Chassis
Slot 1 (if applicable
) _________
_________
Slot 2 (if applicable)
_________
_________
Peripheral Device
_________
_________
Total:
_________
Place Total on this Line --->
_______
W
2.
Convert to BTUs/hr. Multiply the total heat dissipation of your SLC
500 fixed control system by 3.414.
x 3.414
Total heat dissipation of the SLC 500 control system:
_______
BTUs/hr
Example Heat Dissipation
Calculation