Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual
Page 95
Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus
5-13
➋ The logic of the Modbus variable writing function (Operation command) is not influenced.
1336
331B
Multi-SP Usage
H’00000000 (0): OFF
H’00000001 (1): ON
Advanced
Setting
Function
Group
1338
331C
HB ON/OFF
H’00000000 (0): OFF
H’00000001 (1): ON
133A
331D
MB Command Logic
Switching ➋
H’00000000 (0): OFF
H’00000001 (1): ON
133C
331E
Input Error Output
H’00000000 (0): OFF
H’00000001 (1): ON
133E
331F
Input Shift Type
H’00000000 (0): Temperature input 1-point shift
H’00000001 (1): Temperature input 2-point shift
Advanced
Setting
Function
Group
1340
3320
MV at Stop and Error Addition
H’00000000 (0): OFF
H’00000001 (1): ON
1342
3321
ST Stable Range
H’00000001…H’0000270F (0.1…999.9)
1344
3322
RT
H’00000000 (0): OFF
H’00000001 (1): ON
1346
3323
HS Alarm
H’00000000 (0): OFF
H’00000001 (1): ON
1348
3324
LBA Detection Time
H’00000000…H’0000270F (0…9999)
134A
3325
LBA Function Group
H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
134C
3326
LBA Band
H’00000000…H’0000270F
(0.0…999.9 for TC/Pt multi-input models)
(0.00…99.99 for Analog input models)
134E
3327
Soak Time Unit
H’00000000 (0): Minutes
H’00000001 (1): Hours
1350
3328
Alarm SP Selection
H’00000000 (0): Set point during SP ramp
H’00000001 (1): Set point
1356
332B
Manual MV Limit Enable
H’00000000 (0): OFF
H’00000001 (1): ON
135A
332D
PV Rate of Change Calculation
Period
H'00000001 to H'000003E7 (1 to 999)
135C
332E
Automatic Cooling Coefficient
Adjustment
H’00000000 (0): OFF
H’00000001 (1): ON
135E
332F
Heater Overcurrent Use
H’00000000 (0): OFF
H’00000001 (1): ON
1360
3330
Heater Overcurrent Latch
H’00000000 (0): OFF
H’00000001 (1): ON
1362
3331
Heater Overcurrent Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
1364
3332
Control Output 1 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)
1366
3333
Control Output 2 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)
Table 5.10
Address
Parameter Name
Setting (Monitor) Value
Function
Group
Four-byte
mode
Two-byte
mode