Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual
Page 89

Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus
5-7
Table 5.6
Address
Parameter Name
Setting (Monitor) Value
Function Group
Four-byte mode
Two-byte mode
0D06
2D03
Linear Current Output
H'00000000 (0): 4…20 mA
H'00000001 (1): 0…20 mA
Initial Setting function
group
0D1E
2C0F
SP Upper Limit
The range of values (without decimal point) is as
follows:
Temperature: SP lower limit + 1…Input range
upper limit
Analog: SP lower limit + 1…scaling upper limit
0D20
2D10
SP Lower Limit
The range of values (without decimal point) is as
follows:
Temperature: Input range lower limit…SP upper
limit
−
1
Analog: Scaling lower limit…SP upper limit
−
1
0D22
2D11
Standard or Heating
and Cooling
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
0D24
2D12
Direct/Reverse
Operation
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
0D28
2D14
PID/OnOff
H'00000000 (0): ON/OFF
H'00000001 (1): 2 degrees of freedom PID control
0D2A
2D15
ST
H'00000000 (0): OFF
H'00000001 (1): ON
0D2C
2D16
Program Pattern
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
0E00
2E00
Transfer Output Type
H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV monitor (heating)
H'00000005 (5): MV monitor (cooling)