Communications Data for Modbus
5-3
Table 5.2
Address
Parameter Name
Setting (Monitor) Value
Function
Group
Four
Byte
Model
Two
Byte
Model
0500
2500
Operation/Adjustment Protect
H’00000000 (0): No restrictions in Operation and Adjustment function groups
H’00000001 (1): Move to Adjustment function group is prohibited.
H’00000002 (2): Display and change of only PV and PV/SP parameters is
allowed.
H’00000003 (3): Display of only PV and PV/SP parameters is allowed.
Protect
0502
2501
Initial Setting/Communications
Protect
H’00000000 (0): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is displayed.)
H’00000001 (1): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is not
displayed.)
H’00000002 (2): Move to Initial Setting/Communications Setting function
group is prohibited.
0504
2502
Setup Change Protection
H’00000000 (0): OFF (Changing of setup on controller display is allowed.)
H’00000001 (1): ON (Changing of setup on controller display is prohibited.)
0506
2503
PF Key Protect
H’00000000 (0): OFF
H’00000001 (1): ON
0508
2504
Move to Protect function group
H’FFFFF831…H’0000270F (
−
1999…9999)
050A
2505
Password to Move to Protect
function group
H’FFFFF831…H’0000270F (
−
1999…9999)
(Can only be set. The monitor value is always H’00000000.)
050C
2506
Parameter Mask Enable
H’00000000 (0): OFF
H’00000001 (1): ON
0600
2600
Manual Manipulated Variable
(MV)
Standard: H’FFFFFFCE…H’0000041A (
−
5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A (
−
105.0…105.0)
Manual
function
group
0602
2601
Set Point
SP lower limit…SP upper limit
Operation
0608
2508
Heater Current 1 Value Monitor
H’00000000…H’00000226 (0.0…55.0)
060A
2605
MV Monitor (Heating)
Standard: H’FFFFFFCE…H’0000041A (
−
5.0…105.0)
Heating and cooling: H’00000000…H’0000041A (0.0…105.0)
060C
2606
MV Monitor (Cooling)
H’00000000…H’0000041A (0.0…105.0)