beautypg.com

Reading undisplayed parameters, Example command and response, Process value in 4-byte mode – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 69: Figure 4.9, Figure 4.10 process value in 2-byte mode, Figure 4.11 command frame, Write variable area -11, Write variable area

background image

Publication 900-UM004D-EN-E - July 2010

Modbus Communications Procedure

4-11

Reading Undisplayed Parameters

It is possible to read the parameters that are not displayed due to display
settings as well as the parameters that are never displayed in the Controller.

Example Command and Response

The following example shows the command/response when reading the
process value. (In this case, the slave address is H’01.)

Process Value in 4-Byte Mode

Address: H’0000; Read data: H’000003E8 (100.0

°

C)

Figure 4.9

Figure 4.10 Process Value in 2-Byte Mode

Write Variable Area

To write data to the variable area, set the required data in the command frame,
as shown in Figure 4.11.

Figure 4.11 Command Frame

Address: H’2000; Read data: H’03E8 (100.0

°

C)

Command:

Response:

01

01

03

03

02

20 00

00 01

03 E8

8FCA (CRC-16)

B8FA (CRC-16)

Number of

Elements

Slave

address

Function

code

Write

start address

Byte

count

1

1

2

2

1

H'10

2

CRC-16

0 to 208 (2

×

104)

Write data (for the

number of elements)