Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual
Page 47
Publication 900-UM004D-EN-E - July 2010
Communications Data
3-5
Table 3.3 Variable Type C3 (83)
Variable
Type
Address
Item (Parameter)
Set (Monitor) Value
Function
Group
C3 (83)
0000
Input Type (TC/Pt
multi-input models)
➊
H’00000000 (0): Pt (
−
200…850
°
C/
−
300…1500°F)
H’00000001 (1): Pt (
−
199.9…500.0
°
C/
−
199.9…900.0°F)
H’00000002 (2): Pt (0.0…100.0
°
C/0.0…210.0°F)
H’00000003 (3): JPt (
−
199.9…500.0
°
C/
−
199.9…900.0°F)
H’00000004 (4): JPt (0.0…100.0
°
C/0.0…210.0°F)
H’00000005 (5): K (
−
200…1300
°
C/
−
300…2300°F)
H’00000006 (6): K (
−
20.0…500.0
°
C/0.0…900.0°F)
H’00000007 (7): J (
−
100…850
°
C/
−
100…1500°F)
H’00000008 (8): J (
−
20.0…400.0
°
C/0.0…750.0°F)
H’00000009 (9): T (
−
200…400
°
C/
−
300…700°F)
H’0000000A (10): T (
−
199.9…400.0
°
C/
−
199.9…700.0°F)
H’0000000B (11): E (0…600
°
C/0…1100°F)
H’0000000C (12): L (
−
100…850
°
C/
−
100…1500°F)
H’0000000D (13): U (
−
200…400
°
C/
−
300…700°F)
H’0000000E (14): U (
−
199.9…400.0
°
C/
−
199.9…700.0°F)
H’0000000F (15): N (
−
200…1300
°
C/
−
300…2300°F)
H’00000010 (16): R (0…1700
°
C/0…3000°F)
H’00000011 (17): S (0…1700
°
C/0…3000°F)
H’00000012 (18): B (100…1800
°
C/300…3200°F)
H’00000013 (19): Infrared temperature sensor (K 140
°
F/60
°
C)
H’00000014 (20):Infrared temperature sensor (K 240
°
F/120
°
C)
H’00000015 (21):Infrared temperature sensor (K 280
°
F/140
°
C)
H’00000016 (22): Infrared temperature sensor (K 440
°
F/220
°
C)
H’00000017 (23): 0…50 mV
H’00000018 (24): W (0... 2300
°
C/0...3200
°
F)
H’00000019 (25): PL II (0... 1300
°
C/0...2300
°
F)
Initial
setting
Input Type (analog
input models) ➊
H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA
H’00000002 (2): 1…5 V
H’00000003 (3): 0…5 V
H’00000004 (4): 0…10 V
C3 (83)
0001
Scaling Upper Limit
Scaling lower limit +1…0000270F (scaling lower limit +1…9999)
C3 (83)
0002
Scaling Lower Limit
H’FFFFF831 to Scaling upper limit -1 (-1999 to scaling upper limit
-1)
C3 (83)
0003
Decimal Point
Position (TC/Pt
multi-input models)
H’00000000…H’00000001 (0…1)
Decimal Point
Position (analog input
models)
H’00000000…H’00000003 (0…3)
C3 (83)
0004
Temperature Unit
H’00000000(0):
°C
H’00000001(1):
°F
C3 (83)
0005
SP Upper Limit
The range of values (without decimal point) is as follows:
Temperature: SP lower limit + 1 to Input range upper limit
Analog: SP lower limit + 1 to Scaling upper limit
C3 (83)
0006
SP Lower Limit
The range of values (without decimal point) is as follows:
Temperature: Input range lower limit to SP upper limit - 1
Analog: Scaling lower limit to SP upper limit - 1
C3 (83)
0007
PID/ ON/OFF
H’00000000(0)
ON/OFF
H’00000001(1)
2-PID Control
C3 (83)
0008
Standard/Heating
and Cooling
H’00000000(0): Standard
H’00000001 (1)
Heating and cooling
➊
The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
➋
The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
➌
Communications parameters are enabled after they have been changed by resetting the controller.
➍
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
➎
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
➏
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
➐
The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
➑
The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
➒
P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
➓
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.