Communications specifications, Transmission procedure – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual
Page 10

Publication 900-UM004D-EN-E - July 2010
1-2
About Communications Methods
Communications
Specifications
Note:
Highlighted
characters in the table above indicate defaults.
➊ Direct RS-232C communication is only available with the 900-TC8. However, the 900-CONVx25(B) RS232/USB
to RS485 converter can be used for 900-TC16 and 900-TC32 controllers.
➋ Communications speed, data bits, stop bits and vertical parity can each be configured independently in the
controller’s Communications Setting function group.
➌ 900-TC8, 900-TC16, and 900-TC32 Series B controllers only.
➍ The communications data length for Modbus must be 8 bits.
Transmission procedure
When the host device transmits a command frame, the 900-TCx transmits a
response frame that corresponds to the command frame. A single response
frame is returned for each command frame. The following diagram shows the
operation of the command and response frames.
Allow a wait time of at least 2 ms until the next command is sent after the host
device receives a response from the 900-TCx temperature controller.
Table 1.1
Transmission line connection➊
RS-485 : Multiple point, or RS-232C : Point to point
Communications method➊
RS-485 (2-wire, half-duplex), or RS-232C
Synchronization method
Start-stop synchronization
Baud rate
1200, 2400, 4800,
9600
, 19200, 38400, or 57600 bps
Communication code➋
ASCII
Data bits➋
7
or 8 bits
Stop bits➋
1 or
2
bits
Error detection
−
Parity (none,
even
or odd) BCC (block check
character)
−
BCC with CompoWay/F (900-TC)
−
CRC-16 (Cyclic Redundancy Check 16) Modbus➍
communications
Flow control
None
Interface➊
RS-485/RS-232C
Retry function
None
Communications buffer
217 bytes➌, 40 byte
Communications response wait
time
0 to 99 ms, default time: 20 ms
Host Device
900-TCx Temperature Controller
Command Frame
Command Frame
Response Frame