beautypg.com

Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 46

background image

46

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 3

CGCM Unit Operation

To activate droop:

the metering CTs and generator VTs must be properly connected and

configured.

the desired droop setpoint must be written to the V_DroopSetpt tag.
excitation enabled (tag SoftwareExcEn = 1).
remote Excitation Enable On (discrete input).
the CGCM unit must be in AVR mode (tag AVR_FCR_Select = 0).
droop must be enabled (V_DroopEn tag = 1).
droop must be selected (Droop_CCC_Select tag = 0).
automatic reactive power control must be disabled (tag PF_VAR_En = 0).

Cross-current Compensation

Cross-current compensation (reactive differential compensation) is a method of
connecting multiple generators in parallel to share reactive load. Cross-current
compensation requires the connection of an additional CT into the cross-current
compensation input. The CGCM unit operates in a stand-alone application
without the cross-current inputs connected.

The cross-current compensation method of reactive load sharing is possible with
other controllers of similar type. Cross-current compensation monitors the ID
current, V GEN A, and V GEN C inputs to adjust the excitation level. A gain
adjustment is provided to allow tuning of the cross current control. Cross-current
compensation is configured and controlled by using the software interface to the
Logix controller.

To activate cross-current compensation:

the generators must be connected in parallel.
the cross-current CT and generator VTs must be properly connected.
the desired cross-current gain must be written to the CrossCurrentGain

tag.

excitation enabled (tag SoftwareExcEn = 1).
remote Excitation Enable On (discrete input).
the CGCM unit must be in AVR mode

(tag AVR_FCR Select = 0).

droop must be enabled (V_DroopEn tag = 1).
cross-current compensation must be selected (Droop_CCC_Select tag

= 1) (and KVAR_LS_En tag = 1 for firmware rev. 2.

x).

When cross-current compensation is disabled or control power is removed from
the unit, the cross-current input terminals ID(+) and ID(-) are internally
connected together through a very small impedance.

(1)

(1) For series B devices, the input terminals are not connected together when control power is removed.