Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 152
![background image](/manuals/578261/152/background.png)
152
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 7
Troubleshooting
Excitation output is greater than
setpoint
FCR not selected/enabled
Check excitation FCR select
Correct Logix controller logic or I/O
as required
Wiring error
Check wiring for excitation current
output, fuses open, grounding, and
PMG/supply
Correct wiring as required
Gain mis-adjusted
Check gains entered into CGCM unit
configuration
Calculate/adjust as required
Excitation is erratic/unstable
Gain mis-adjusted
Check gains entered into CGCM unit
configuration
Calculate/adjust as required
Wiring error
Check wiring for excitation enable,
excitation current output, fuses
open, grounding, and PMG/supply
Correct wiring as required
Table 19 - Excitation Control - FCR
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Table 20 - Excitation Control - AVR
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
No excitation current output
Excitation is not enabled
Check excitation enable (hardware
and software) and AVR select
Correct Logix controller logic or I/O
as required
Wiring error
Check wiring for excitation enable,
excitation current output, VT inputs,
fuses open, grounding, and
PMG/supply
Correct wiring as required
No supply/PMG power
Measure Voltage at CGCM unit
PMG / supply input terminals
Correct supply anomaly if
insufficient voltage is measured