Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 137
![background image](/manuals/578261/137/background.png)
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
137
CGCM Unit Software Interface Chapter 6
3
1
Bool
0
AutoSyncEn
Auto Synchronization Enable
-
0=Disabled,
1=Enabled
Bool
1
CheckSyncEn
Check Synchronization Enable
Bool
2
PermissiveSyncEn
Permissive Synchronization
Enable
Bool
3
Spare5
Bool
4
Spare6
Bool
5
Bus A_B_Select
Bus A/B Select
0=Bus A, 1=Bus B
Bool
6
DeadBusClosureEn
Dead Bus Closure Enable
0=Disabled,
1=Enabled
Bool
7
InitiateSync
Initiate Synchronization
0=Inactive, 1=Active
4
1
Bool
0
Clear_kW_Hrs (Rev. 2.x)
Set_kW_Hrs (Rev. 3.x or later)
Set/Clear kW Hours
0=De-assert,
1=Assert
Bool
1
Clear_kVAR_Hrs (Rev. 2.x)
Set_kVAR_Hrs (Rev. 3.x or later)
Set/Clear kVAR Hours
Bool
2
Clear_kVA_Hrs (Rev. 2.x)
Set_kVA_Hrs (Rev. 3.x or later)
Set/Clear kVA Hours
Bool
3
Spare7
Bool
4
Droop_CCC_Select
Droop/Cross Current
Compensation Select
0=Droop, 1=CCC
Bool
5
V_DroopEn
Voltage Droop Enable
0=Disabled,
1=Enabled
Bool
6
Spare8
Bool
7
SoftwareExcEn
Software Excitation Enable
0=Disabled,
1=Enabled
5
1
Bool
0
Spare9
-
-
Bool
1
Spare10
Bool
2
Spare11
Bool
3
Spare12
Bool
4
kVAR_LS_BridgeEn
kVAR Load Share Bridge Enable
0=Disabled,
1=Enabled
Bool
5
kVAR_LS_En
kVAR Load Share Enable
Bool
6
kW_LS_BridgeEn
kW Load Share Bridge Enable
Bool
7
kW_LS_En
kW Load Share Enable
6
1
Bool
0…7
Spare13_20
-
-
7
1
Bool
0…7
Spare21_28
-
-
8
4
Real
N/A
AVRSetpt
Automatic Voltage Regulator
Setpoint
Volts
85…30,000
12
4
Real
N/A
FCRSetpt
Field Current Regulator Setpoint
Adc
0…15
16
4
Real
N/A
PFSetpt
Power Factor Setpoint
PF
-0.5…0.5
20
4
Real
N/A
VARSetpt
VAR Setpoint
VARS
-1E+07…1E+07
24
4
Real
N/A
kWLSOutV
kW Load Share Output Voltage
Volts
28
4
Real
N/A
kWAnalogTargetPUValue
kW Analog Target Value Per Unit -
Table 10 - Output (scheduled write) Data Table, Assembly Instance 1
Byte
Size
in
Bytes
Type
Bits
Tag Name
Description
Units
Range