Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

201

Specifications Appendix D

Regulation

The following modes are used to regulate the CGCM unit.

AVR Operating Mode

Accuracy: ±0.25% over the load range at rated power factor and constant

generator frequency.

Steady State Stability: ±0.1% at constant load and generator frequency.
Temperature Drift: The maximum error due to temperature drift will be

0.005% of full scale per degrees Celsius for voltage and current
measurements and 0.010% of full scale per degree Celsius for watt and
VAR measurements.

V/Hz Characteristic: Slope from 0 to 3PU is adjustable in 0.1PU

increments. Two knees and two slopes are available.

Response Time: < 1 cycle.

FCR Operating Mode

Accuracy: ±1% of rated current.

VAR Operating Mode

Accuracy: ±0.4% of the nominal VA rating at the rated frequency.

Power Factor Mode

Accuracy: ±0.02% of the PF setpoint for the real power between

10…100% at the rated frequency.

Parallel Compensation

Loss of Excitation

Attribute

1407-CGCM

Modes

Reactive Droop

Reactive Differential (cross-current)

Droop adjust range

0…30%

Accuracy

±0.3% of rated cross current input current

Line-drop compensation range

0…10% of rated voltage in 0.1% increments

Attribute

Range

Increment

Pickup

0.1…15 A

0.1 A

Time delay

0.1…9.9 s

0.1 s