Regulation, Parallel compensation loss of excitation – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 201
![background image](/manuals/578261/201/background.png)
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
201
Specifications Appendix D
Regulation
The following modes are used to regulate the CGCM unit.
AVR Operating Mode
• Accuracy: ±0.25% over the load range at rated power factor and constant
generator frequency.
• Steady State Stability: ±0.1% at constant load and generator frequency.
• Temperature Drift: The maximum error due to temperature drift will be
0.005% of full scale per degrees Celsius for voltage and current
measurements and 0.010% of full scale per degree Celsius for watt and
VAR measurements.
• V/Hz Characteristic: Slope from 0 to 3PU is adjustable in 0.1PU
increments. Two knees and two slopes are available.
• Response Time: < 1 cycle.
FCR Operating Mode
• Accuracy: ±1% of rated current.
VAR Operating Mode
• Accuracy: ±0.4% of the nominal VA rating at the rated frequency.
Power Factor Mode
• Accuracy: ±0.02% of the PF setpoint for the real power between
10…100% at the rated frequency.
Parallel Compensation
Loss of Excitation
Attribute
1407-CGCM
Modes
Reactive Droop
Reactive Differential (cross-current)
Droop adjust range
0…30%
Accuracy
±0.3% of rated cross current input current
Line-drop compensation range
0…10% of rated voltage in 0.1% increments
Attribute
Range
Increment
Pickup
0.1…15 A
0.1 A
Time delay
0.1…9.9 s
0.1 s