Unscheduled Write Data Table

The Unscheduled Write data table contains gains and other configuration
parameters, that can be written to the CGCM unit by the ControlLogix
controller regardless of the excitation state.

Data in this Controller Tag is written by the host controller to the unit by using
unscheduled messaging controlled by the user program.

Data Type

The Unscheduled Write data table is automatically created by using the
appropriate module-defined data type depending on the CGCM unit firmware
revision.

Assembly Object Instance 6 - Unscheduled Write Data Table

The Get Attributes Single service for instance 6 of the Assembly Object can
access the following information.

The Set Attributes Single

service for instance 6 of the Assembly Object can access

the following information.

Configuration Checking

When an unscheduled write is received, the CGCM unit verifies that individual
parameters are within the range indicated in the table below (for example,
perform range checking). If an out-of-range parameter is detected, the CGCM
unit ignores all data in the unscheduled write in the message instruction. The
CGCM unit does not perform application checking (is a value suitable for the
particular application) or dependency checking (is a value reasonable based on
other values entered).

Table 13 - Get Attributes Single (service code 0x0E)

Name

Attribute ID

Data Type

Value

Data

3

UINT

See Unscheduled Write Data

Table, Assembly Instance 6

Size

4

UINT

CGCM firmware 2.x = 64

CGCM firmware 3.x = 72

Table 14 - Set Attributes Single (service code 0x10)

Name

Attribute ID

Data Type

Value

Data

3

UINT

See Unscheduled Write Data Table,

Assembly Instance 6