Protection – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 163
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
163
Troubleshooting Chapter 7
Protection
One or both CGCM units will not
operate as primary
Faulty wiring
Measure excitation enable input to
CGCM unit that will not act as
primary
Verify voltage is applied to
excitation enable input terminal
Check operation of external relay
and associated wiring for
redundancy relay and output
Correct excitation redundancy relay
operation
Check wiring of excitation +/- output
from CGCM unit
Correct excitation output wiring
Logix controller error
Check output to excitation enable
input (hardware and software)
Correct logic as required
Check logic to redundancy relay (if
applicable)
Correct logic as required
One CGCM unit has failed or is not
configured properly
Troubleshoot as non-redundant
CGCM unit
Correct or replace as needed
Table 32 - Redundancy
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Table 33 - Protection
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Loss of excitation current (40)
Wiring error
Check excitation output wiring
Correct wiring as required
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
Over-excitation voltage (59F)
Wiring error
Check excitation output wiring
Correct wiring as required
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
OEL limit exceeded
Check OEL operation
Correct as required
Generator over-voltage (59)
Rapid loss of large load
Gains mis-adjusted
Check AVR gains
Calculate/adjust gains as required
Generator under-voltage (27)
Over load
Wiring error
Check VT wiring. See Voltage
metering trouble shooting
Correct wiring as required
Loss of sensing (60FL)
Fuse open
Check VT fuses
Replace as required
Wiring error
Check for open connections and
phase rotation reversal
Correct wiring as required