Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 164
164
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 7
Troubleshooting
Loss of permanent magnet
generator (PMG/Excitation power)
(27)
Supply circuit breaker trip/fuse open Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Correct/replace PMG input
protection as required
Wiring error
Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Correct wiring as required
PMG failure
Check PMG supply. Measure with
voltmeter at CGCM unit PMG input
terminals
Repair as required
Incorrect configuration
Check single-phase versus 3-phase
selection
Correct as required
Reverse var (40Q)
Under-excitation
Check UEL configuration if required, Correct as required
Incorrect operating mode selected
Check selected operating mode for
operating requirements
Select as appropriate
Over-frequency (81O)
Governor error
Correct as required
Under-frequency (81U)
Governor error
Correct as required
Reverse power (32R)
Governor error
Correct as required
Rotating diode monitor
Failed diode
Remove and test diodes
Replace diode
Incorrect configuration
Confirm test / set up of diode
monitor parameters with active
parameters
Correct as required
Insufficient number of fly back
diodes installed
Check number of external flyback
diodes installed at CGCM excitation
output if required
Install as required
Phase rotation error (47)
Wiring error
See troubleshooting voltage
metering
Correct wiring as required
Generator over-current (51)
Fault or large load condition
Incorrect configuration
Check configuration
Correct as required
Table 33 - Protection
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action