Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 6
CGCM Unit Software Interface
The Set Attributes Single
service for instance 6 of the Assembly Object can access
the following information.
Configuration Checking
When configuration data is received, the CGCM unit verifies that individual
parameters are within the minimum and maximum values indicated in the table
below (for example, perform range checking). If an out-of-range parameter is
detected, the CGCM unit enters a configuration fault mode and ignores all data
in the configuration write. The Connection tab in the module configuration
dialog box in RSLogix 5000 software displays an error code corresponding to the
first offending configuration parameter. The CGCM unit does not perform any
application checking (for example, is a value suitable for the particular
application) or dependency checking (for example, is a value reasonable based on
other values entered).
Data Table
Table 17 - Set Attributes Single (service code 0x10)
Name
Attribute ID
Data Type
Value
Data
3
UINT
See Unscheduled Configuration
Read/Write Data Table, Assembly
Instance 4
IMPORTANT
Use of this service is not recommended. See the note above.
Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4
Byte
Size in
Bytes
Type
Bits
Tag Name
Description
Units
Range
Error Code
0
1
SINT
N/A
Space Reserved for Logix controller Revision Configuration Number
1
3
SINT
N/A
Pad Bytes Reserved for Logix controller Usage
4
1
Bool
0
RevVARFltOutEn
Reverse VAR Fault Output
Enable
-
0=Disabled,
1=Enabled
Bool
1
RevPwrFltOutEn
Reverse Power Fault Output
Enable
Bool
2
OvrExcFltOutEn
Over-excitation Fault Output
Enable
Bool
3
Ovr_I_FltOutEn
Over-current Fault Output
Enable
Bool
4
Undr_V_FltOutEn
Under-voltage Fault Output
Enable
Bool
5
OvrVFltOutEn
Over-voltage Fault Output
Enable
Bool
6
UndrFreqFltOutEn
Under-frequency Fault
Output Enable
Bool
7
OvrFreqFltOutEn
Over-frequency Fault Output
Enable