Specifications
Environment
Agency Certifications
Physical Characteristics
Attribute
1407-CGCM
Temperature, operating
-20…70 °C (-4…158 °F)
Temperature, storage
-40…85 °C (-40…185 °F)
Humidity, operating
5…95% (noncondensing)
Shock, operating
30 g
Shock, nonoperating
50 g in 3 perpendicular planes
Vibration, operating
10 … 500 Hz, 5.0 g / 0.015 in. max (p-p)
2 hours each axis
Dielectric strength
Tested per IEEE 421.3
Salt fog
Tested per MIL-STD-810E, Method 509.3
Region
(1)
,
(2)
,
(3)
Certification / Compliance
Standard
USA and Canada
Class I, Zone 2,
AEx nC IIC T3, Ex nL IIC T3 Gc X
UL 60079-15 3rd Edition/ CSA 60079-15:12
UL 60079-0 5th Edition/ CSA 60079-0:11
Class I, Division 2, Groups A, B, C, or D
UL File E220640
ANSI/ISA 12.12.01-2012 / CSA C22.2 No. 213-M1987
Europe
II 3G Ex nL IIC Gc (DEMKO 13 ATEX 1202591U)
EN 60079-0:2009
EN 60079-15:2005
CE Compliance
EN 60947-1: Low voltage switch and control gear requirements
EN 50081-2: Electromagnetic compatibility emissions
EN 61000-4-2: Electromagnetic compatibility immunity
EN 61000-4-2: ESD Immunity
ENV 50204: Radiated immunity (Pulse)
EN 61000-4-3: Radiated immunity (Continuous)
EN 61000-4-4: Fast transient immunity
EN 61000-4-5: Surge immunity
EN 61000-4-6: Conducted immunity
EN 61000-4-8: Power frequency magnetic field
EN 55011: Conducted emissions/ Radiated emissions
EN 61000-4-11: Line related tests
(1) This equipment is intended to be mounted inside a suitable ATEX certified enclosure providing a minimum of IP54 protection.
(2) This equipment is intended for use in a Pollution Degree 2 industrial environment or better.
(3) The device is to be powered by a 24V Nominal Battery or 24V DC Power Supply with ATEX certification.
Attribute
1407-CGCM
Width
247.7 mm (9.75 in.)
Height
355.6 mm (14.00 in.)
Depth
209.6 mm (8.25 in.)
Weight
7.7 kg (17 lb)
Heat dissipation
3.1 kW max