Installation Chapter 2

Excitation Output

The excitation outputs are on TB2 and are labeled EXC(+) and EXC(-).
Twisted, shielded cabling is required for the excitation outputs.

Figure 7 - Excitation Output Connections, Non-redundant CGCM

When the redundancy function is used, three or four external flyback diodes in
series must be placed across the generator field winding.

Refer to the redundancy wiring diagrams on pages

31

32

.

Control Power

The 24V DC control power inputs are on TB4 and are labeled BAT(+) and
BAT(-).

Figure 8 - Control Power and Chassis Ground Connections

TB2

Shld2

Shld2

EXC (-)
EXC (+)

Exciter field

Exciter voltage
connections

TB4

BA T (+)
BA T(-)
FL T
RD RLY
CH GND

24 VDCControl

Power Sour ce

Grou nd st ud

(ty pical)

Ground bus

CGCM