Table 41 - pcp object instance attributes, Table 42 - pcp object common services, Tcp/ip interface object — class code 0xf5 – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 92
![background image](/manuals/578085/92/background.png)
92
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
The following instance attributes are implemented for all parameter attributes:
The following common services are implemented for the PCP Object:
TCP/IP Interface Object — CLASS CODE 0xF5
The following class attributes are supported for the TCP/IP Interface Object:
The following instance attributes are implemented for all parameter attributes:
Table 41 - PCP Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get/Set
MCC Number
USINT
0-255
2
Get/Set
Vertical Section Number
USINT
0-255
3
Get/Set
Starting Section Letter
USINT
0-255
4
Get/Set
Space Factors
USINT
0-0x3F
5
Get/Set
Cabinet Width
USINT
0-255
6
Get/Set
Controlled Device
USINT
0-255
7
Get
Number of Device Inputs
USINT
2
8
Get/Set
Devices Connected at Inputs
Array of USINT
9
Get
Number of Device Outputs
USINT
1
10
Get/Set
Devices Connected at Outputs
Array of USINT
Table 42 - PCP Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
0x01
No
Yes
Get Attribute All
0x02
No
Yes
Set Attribute All
0x0E
Yes
Yes
Get Attribute Single
0x10
No
Yes
Set Attribute Single
Table 43 - TCP/IP Interface Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
1
Table 44 - TCP/IP Interface Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Status
DWORD
N/A
2
Get
Configuration capability
DWORD
0x00000014
3
Get/Set
Configuration control
DWORD
N/A