Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 66
66
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 6
Warning Enable
Parameter
No.
13
This parameter allows the installer to enable or disable the warning
functions separately. All warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled
Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Access Rule
Get/Set
Data Type
WORD
Units
—
Min. Value
0x0000
Max. Value
0x007F
Default Value
0x0000
Single/Three Ph
Parameter No.
15
This parameter configures the EtherNet/IP
Module for single- or three-phase application.
This parameter should be set to “Single Phase"
when Bulletin 193S or 592S devices are
employed.
0 = Single Phase
1 = Three Phase
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
1
Tag Name
Single_Three_Ph
OL Reset Mode
Parameter No.
16
This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment while
the SMM is powered. Note, however, that the E1
Plus manual reset button, accessible at the front,
is always active.
0 = Manual
1 = Automatic
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
OL_Reset_Mode
OL Warning Level
Parameter No.
17
This parameter sets the overload warning level.
Access Rule
Get/Set
Data Type
USINT
Units
% TCU
Min. Value
0
Max. Value
100
Default Value
90
Tag Name
OL_Warning_Level