Chapter 6

Warning Enable

Parameter
No.

13

This parameter allows the installer to enable or disable the warning
functions separately. All warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled
Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle

Access Rule

Get/Set

Data Type

WORD

Units

Min. Value

0x0000

Max. Value

0x007F

Default Value

0x0000

Single/Three Ph

Parameter No.

15

This parameter configures the EtherNet/IP
Module for single- or three-phase application.
This parameter should be set to “Single Phase"
when Bulletin 193S or 592S devices are
employed.
0 = Single Phase
1 = Three Phase

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

1

Tag Name

Single_Three_Ph

OL Reset Mode

Parameter No.

16

This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment while
the SMM is powered. Note, however, that the E1
Plus manual reset button, accessible at the front,
is always active.
0 = Manual
1 = Automatic

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OL_Reset_Mode

OL Warning Level

Parameter No.

17

This parameter sets the overload warning level.

Access Rule

Get/Set

Data Type

USINT

Units

% TCU

Min. Value

0

Max. Value

100

Default Value

90

Tag Name

OL_Warning_Level