I/o setup group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 69
![background image](/manuals/578085/69/background.png)
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
69
Chapter 6
I/O Setup Group
Set To Defaults
Parameter No.
25
This parameter allows the user to reset the
parameter settings to the factory default values.
After parameter values have been reset to the
factory default settings, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Defaults
Note: A transition from 0 to 1 is necessary to
trigger a set to default when mapped on the cyclic
data.
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
Set_To_Default
OutA Pr FltState
Parameter No.
34
This parameter, in conjunction with the Pr
FltValue, defines how Output A will respond when
a trip occurs. When set to “1”, Output A will
continue to operate as commanded via the
network. When set to “0”, Output A will open or
close as determined by the setting of the Pr
FltValue.
0 = Go to FltValue
1 = Ignore Fault
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
OutA_Pr_FLTState
OutA Pr FltValue
Parameter No.
35
This parameter determines the state that Output A
assumes when a trip occurs and the Pr FltState is
set to “0”.
0 = Open
1 = Closed
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
OutA_Pr_FLTValue
OutA En FltState
Parameter No.
36
This parameter, in conjunction with the FltValue,
defines how Output A will respond when a
EtherNet/IP network fault occurs. When set to
“1”, Output A will hold the state prior to trip
occurrence. When set to “0”, Output A will open
or close as determined by the setting of the
FltValue.
0 = Go to FltValue
1 = Hold Last State
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
OutA_En_FLTState