Table 23 - ethernet object common services, Connection manager object — class code 0x06, Discrete input point object — class code 0x08 – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 85
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
85
Appendix B
The following services are implemented for the Assembly Object:
Connection Manager Object — CLASS CODE 0x06
No class or instance attributes are supported.
The following common service
are implemented for the Connection Manager
Object:
Discrete Input Point Object — CLASS CODE 0x08
The following class attributes are supported for the Discrete Input Point Object:
16
Trip Log 2 (low byte)
17
Trip Log 2 (high byte)
18
Trip Log 3 (low byte)
19
Trip Log 3 (high byte)
20
Trip Log 4 (low byte)
21
Trip Log 4 (high byte)
Table 23 - EtherNet Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
Consuming
Instance
Producing
0x0E
Yes
Yes
Yes
Get Attribute Single
0x10
No
Yes
No
Set Attribute Single
Table 24 - Connection Manager Object Common Services
Service Code
Implemented for:
Service Name
Class
Instance
0x54
No
Yes
Forward Open
0x4E
No
Yes
Forward Close
Table 25 - Discrete Input Point Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
0x0002
2
Get
Max Instance
UINT
0x0002
Table 22 - Instance 111 —Complete Motor Starter Input Assembly
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0