Click "apply changes" to save the configuration, Limitations – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 61

Rockwell Automation Publication 193-UM012B-EN-P - June 2011
61
Chapter 5
4.
Enter the Device Identity information into the fields as described below.
5.
Click "Apply Changes" to save the configuration.
Limitations
Based on the functionality of the E1 Plus EtherNet/IP module there are some
limitations on when emails can be triggered.
• If two events occur at the same time, an email will only be sent for the most
significant event.
• If the module has been configured to send an email for a lower prioritized
event and this event occurs at the same time as a higher prioritized event
for which the module has not been programmed to send an email, no email
will be sent for either event.
• The Clear email will only be sent when all events have been cleared and an
event email has previously been sent. For example: if the module is
configured to send an email when a jam trip is detected and it detects an
overload trip for which no email notification is configured, no email will be
sent when the overload event is cleared.
Device Name
The name of the E1 Plus EtherNet/IP module.
Device Description
The description of the E1 Plus EtherNet/IP module.
Device Location
The location of the E1 Plus EtherNet/IP module.
Contact Info
Contact information for the E1 Plus EtherNet/IP module.