Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 90
90
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
The following common services are implemented for the Control Supervisor
Object:
101
Get
Warning Status
WORD
Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7=Non Vol Mem Fault
Bit 8-Bit 15=Not used
102
Get
Trip Log 0
WORD
Last trip condition. Bit definitions of the value are the same as attribute 101
103
Get
Trip Log 1
WORD
Last trip condition. Bit definitions of the value are the same as attribute 101
104
Get
Trip Log 2
WORD
Last trip condition. Bit definitions of the value are the same as attribute 101
105
Get
Trip Log 3
WORD
Last trip condition. Bit definitions of the value are the same as attribute 101
106
Get
Trip Log 4
WORD
Last trip condition. Bit definitions of the value are the same as attribute 101
107
Get
Device Status
WORD
Bit 0=Trip
Bit 1=Warning
Bit 2=OutputA
Bit 3=Input 1
Bit 4=Input 2
Bit 5=Motor Current
Bit 6-Bit 15=Not used
108
Get/Set
Trip Enable
WORD
Bit 0=Not Used
Bit 1=Not Used
Bit 2=Jam
Bit 3-Bit 15=Not Used
109
Get/Set
Warning Enable
WORD
Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7-Bit 15=Not Used
110
Get/Set
OL Reset Mode
BOOL
0=Manual
1=Automatic
111
Get/Set
IN1 Assignment
USINT
0=Normal
1=Trip Reset
2=OL Contact
112
Get/Set
IN2 Assignment
USINT
0=Normal
1=Trip Reset
2=OL Contact
Table 37 - Control Supervisor Object Instance 1 Attributes
Attribute ID
Access Rule
Name
Data Type
Value
Table 38 - Control Supervisor Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get Attribute Single
0x10
No
Yes
Set Attribute Single
0x05
No
Yes
Reset