Parameter group listing, Table 6 - parameter groups, Monitor group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 64: Parameter group listing monitor group

64
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 6
Parameter Group Listing
The E1 Plus EtherNet/IP Module contains five parameter groups
Monitor Group
Table 6 - Parameter Groups
Monitor parameters
Advanced Setup
Reset/Lock
I/O Setup
Trip History
1 Average %FLA
12 Trip Enable
14 Trip Reset
34 OutA Pr FltState
5 Trip Log 0
2%Therm Utilized
13 Warning Enable
24 Program Lock
35 OutA Pr FltValue
6 Trip Log 1
3 Trip Status
15 Single/Three Ph
25 Set to Default
36 OutA En FltState
7 Trip Log 2
4 Warning Status
16 OL Reset Mode
37 OutA En FltValue
8 Trip Log 3
10 Device Status
17 OL Warning Level
38 OutA En IdlState
9 Trip Log 4
18 Jam Inhibit Time
39 OutA En IdlValue
19 Jam Trip Delay
40 IN1 Assignment
20 Jam Trip Level
41 IN2 Assignment
21 Jam Warn Level
22 UL Inhibit Time
23 UL Warn Level
Average %FLA
Parameter No.
1
This parameter reports the average motor current.
The value is reported as a percentage of motor
rated current (dial setting on the E1 Plus Overload
Relay), and is reported in increments of 5.
Access Rule
Get
Data Type
UINT
Units
%
Min. Value
0
Max. Value
1275
Default Value
0
Tag Name
Average_%FLA
% Therm Utilized
Parameter No.
2
This parameter reports the percent thermal
utilization of the connected motor.
Access Rule
Get
Data Type
USINT
Units
%
Min. Value
0
Max. Value
100
Default Value
None
Tag Name
%_Therm_Utilized