Table 11 - identity object instance attributes, Table 12 - identity object common services, Message router object — class code 0x02 – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 82
82
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Appendix B
Identity Object instances contain the following instance attributes:
The following common services are implemented for the Identity Object:
Message Router Object — CLASS CODE 0x02
No class or instance attributes are supported. The message router object exists
only to rout explicit messages to other objects.
Table 11 - Identity Object Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Vendor ID
UINT
Programmable via test object
2
Get Device
Type
UINT
0x0003
3
Get
Product Code
UINT
300
4
Get Revision
Structure
of:
Major Revision
USINT
1
Minor Revision
USINT
N/A
5
Get
Status
WORD
Bit 0: Owned, shall be set when at least one connection i
configured
Bit 1: Reserved, set to 0
Bit 2: Configured
Bit 3: Reserved, set to 0
Bit 4-7: See extended device status
Bit 8: Minor Recoverable fault
BIt 9: Minor Unrecoverable fault
Bit 10: Major Recoverable fault
Bit 11: Major Unrecoverable fault
Bit 12-15: Reserved, set to 0
Extended device status (Bit 4-7)
0000=Unknown
0001=Firmware updated in progress
0010=Faulted I/O connection
0011=No I/O connection established
0100=Non volatile configuration bad
0101=Major fault
0110=Connection in run mode
0111=Connection in idle mode
6
Get
Serial Number
UDINT
Unique number assigned for each device
7
Get
Product Name
SHORT_STRING
Product name
8
Get State
USINT
3=Operational
Table 12 - Identity Object Common Services
Service Code
Implemented for:
Service Name
Class
Instance
0x01
No
Yes
Get Attribute All
0x0E
Yes
Yes
Get Attribute Single
0x05
No
Yes
Reset