Terminals
IN 1:
IN 2:
SSV (Sensor Supply Voltage)
1
2
3
Supply Voltage (provided by module)
24V DC±10%
Type of Inputs
Current Sinking
ON-State Voltage
15V DC
On-State Current (turn-on)
2 mA
Steady State Current
5 mA
Off-State Voltage
5V DC
Off-State Current
0.5 mA
Transition Voltage
5…15V DC
Transition Current
0.5…2.0 mA
Environmental Ratings:
Ambient Temperature T
amb
Storage
Operating
(Open)
(Enclosed)
-40…+85°C (-40…+185°F)
-20…+60°C (-4…+140°F)
-20…+40°C (-4…+104°F)
Humidity
Operating
Damp Heat - Steady State
Damp Heat - Cyclic
5…95% non-condensing
per IEC 68-2-3
per IEC 68-2-30
Cooling Method
Natural Convection
Vibration (per IEC 68-2-6)
3 G
Shock (per IEC 68-2-27)
30 G
Maximum Altitude
2000 m
Pollution Environment
Pollution Degree 2
Terminal Marking
EN 50012
Degree of Protection
IP20
Electromagnetic Compatibility
Electrostatic Discharge Immunity
Test Level
Performance Criteria
8 kV Air Discharge; 4 kV Contact Discharge
1➊➋
RF Immunity
Test Level
Performance Criteria
10V/m
1➊➋
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
2 kV (Power); 1 kV (control)
1➊➋
Surge Immunity
Test Level
Performance Criteria
2 kV L-E; 1 kV L-L
1➊➋
Radiated Emissions
Class A
Conducted Emissions
Not tested
➊
Performance Criteria 1 requires the DUT (device under test) not to experience degradation or loss of
performance.
➋
Environment 2 - Heavy Industrial.