Reset/lock group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 68
![background image](/manuals/578085/68/background.png)
68
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 6
Reset/Lock Group
UL Inhibit Time
Parameter No.
22
This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.
Access Rule
Get/Set
Data Type
USINT
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10
Tag Name
UL_Inhibit_Time
UL Warn Level
Parameter No.
23
This parameter sets the underload warning level.
Access Rule
Get/Set
Data Type
USINT
Units
% FLA
Min. Value
30
Max. Value
100
Default Value
70
Tag Name
UL_Warn_Level
Trip Reset
Parameter No.
14
This parameter provides the user with the
capability of resetting a trip over the EtherNet/IP
network. After a trip is reset, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Trip
Note: A transition from 0 to 1 is necessary to
trigger a trip reset when mapped on the cyclic
data.
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
Trip_Reset
Program Lock
Parameter No.
24
This parameter prohibits the device parameters
from being altered when set to “Locked”. It must
be set to “Unlocked” to allow parameter
modification.
It doesn’t affect parameters when they’re
accessed through the assembly object.
0 = Unlocked
1 = Locked
Access Rule
Get/Set
Data Type
BOOL
Units
—
Min. Value
0
Max. Value
1
Default Value
0
Tag Name
Program_Lock