beautypg.com

Rockwell Automation 20A PowerFlex 70 Adjustable Frequency AC Drive User Manual

Page 9

background image

Rockwell Automation Publication 20A-IN009D-EN-P - June 2013

9

PowerFlex 70 Adjustable Frequency AC Drive

Essential Requirements for CE Compliance

These six conditions must be satisfied for PowerFlex drives to meet the
requirements of EN61800-3:

Standard PowerFlex 70 CE compatible drive.

Review important precautions/attention statements throughout this

manual before installing the drive.

Ground the drive as described in

General Grounding Requirements on

page 22

.

Output power, control (I/O), and signal wiring must be braided, shielded

cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.

All shielded cables must terminate with the proper shielded connector.

Comply with the conditions in

Table 1

.

Table 1 - PowerFlex 70 EN61800-3 EMC Compatibility

Frame

Drive Description

Second Environment

First
Environment
Restricted
Distribution

Restrict Motor
Cable to 40 m
(131 ft)

Internal
Filter
Option

External
Filter

Input Ferrite

(1)

(1) Input cables through a Ferrite Core (frames A, B, and C Fair-Rite #2643102002 or equivalent, frames D and E Fair-Rite #2643251002

or equivalent).

A

Drive only

X

X

See PowerFlex
Reference
Manual,
publication

PFLEX-RM001

With any comm option

X

X

With remote I/O

X

X

X

B

Drive only

X

X

With any comm option

X

X

With remote I/O

X

X

X

C, D, E

Drive only

X

With any comm option

X

With remote I/O

X

X