Rockwell Automation Publication 20A-IN009D-EN-P - June 2013

47

PowerFlex 70 Adjustable Frequency AC Drive

Running S.M.A.R.T. Start

During a startup, the majority of applications require changes to a few
parameters. The LCD HIM on a PowerFlex 70 drive offers S.M.A.R.T. start, and
displays the most commonly changed parameters. With these parameters you can
set the following functions:

S – Start Mode and Stop Mode

M – Minimum and Maximum Speed

A – Accel Time 1 and Decel Time 1

R – Reference Source

T – Thermal Motor Overload

To run a S.M.A.R.T. start routine, follow the steps in this table:

Running an Assisted Startup

The assisted start-up routine prompts you to input required information. Access
assisted startup by selecting Start Up from the Main Menu.

To perform an assisted startup, follow the steps in this table:

Step

Key(s)

Example LCD Displays

1. Press ALT and then Esc (S.M.A.R.T). The S.M.A.R.T. start

screen appears.

2. View and change parameter values as desired. For HIM

information, see Appendix B.

3. Press Esc to exit the S.M.A.R.T. start.

IMPORTANT

This start-up routine requires an LCD HIM.

Step

Key(s)

Example LCD Displays

1. In the Main Menu, press the up arrow or down arrow to

scroll to Start Up.

2. Press Enter.

IMPORTANT

You must select Done/Exit after you complete the start-up routine for the
start-up/autotune data to be saved.

ALT

Esc

Esc

F-> Stopped

Auto

0.0

Hz

Main Menu:
Diagnostics
Parameter

SMART List:
Digital In2 Sel
Stop Mode A
Minimum Speed

F-> Stopped

Auto

0.0

Hz

Main Menu:
Memory Storage

Start Up

Preferences