beautypg.com

Power terminal block – Rockwell Automation 20A PowerFlex 70 Adjustable Frequency AC Drive User Manual

Page 20

background image

20

Rockwell Automation Publication 20A-IN009D-EN-P - June 2013

PowerFlex 70 Adjustable Frequency AC Drive

Power Terminal Block

Figure 7 - Typical Power Terminal Block Location (B frame shown)

Table 5 - Power Terminal Block Specifications

Table 6 - Wire Routing Recommendations

No.

Name

Frame

Description

Wire Size Range

(1)

(1) Maximum/minimum sizes that the terminal block can accept – these are not recommendations.

Torque

Max
mm

2

(AWG)

Min
mm

2

(AWG)

Max
N•m (lb•in)

Recommended
N•m (lb•in)

Power
terminal block

A, B, C

Input power and
motor
connections

4.0 (10)

0.3 (22)

1.1 (10)

0.8 (7)

D

Input power and
motor
connections

10.0 (6)

0.8 (18)

1.7 (15)

1.4 (12)

E

Input power and
motor
connections

25.0 (3)

2.5 (14)

2.71 (24)

2.71 (24)

SHLD terminal

All

Terminating
point for wiring
shields

1.6 (14)

1.6 (14)

No.

Description

Suggested entry for incoming line wiring.

Suggested entry for motor wiring.

IP 20 (NEMA/UL Type 1)